Skip to content
LANRUN
HXGN-12 product image 1
HXGN-12 product image 1
HXGN-12 product image 2
HXGN-12 product image 3

High-voltage series

HXGN-12

HXGN fixed-type AC metal-enclosed switchgear. The HXGN□-12 series AC metal ring-main switchgear uses an SF6 load-break switch as the main switch, with the entire enclosure air-insulated. It is a compact, extensible metal-enclosed ring-main switchgear suitable for distribution automation. It features simple structure, flexible operation, reliable interlocking and easy installation. It provides corresponding technical solutions for various applications and user requirements. The load-break switch and circuit breaker can be operated manually or electrically; with optional electric operating mechanisms and communication devices, distribution automation functions can be achieved.

Request a quote

Please provide your operating conditions, quantity and required connection or output.

Technical details

Specifications from source material

HXGN fixed-type AC metal-enclosed switchgear. The HXGN□-12 series AC metal ring-main switchgear uses an SF6 load-break switch as the main switch, with the entire enclosure air-insulated. It is a compact, extensible metal-enclosed ring-main switchgear suitable for distribution automation. It features simple structure, flexible operation, reliable interlocking and easy installation. It provides corresponding technical solutions for various applications and user requirements. The load-break switch and circuit breaker can be operated manually or electrically; with optional electric operating mechanisms and communication devices, distribution automation functions can be achieved.

Ambient air temperature
upper limit +40°C, lower limit -10°C in general areas. 2
Altitude
not exceeding 2000 m. 3
Humidity
relative humidity daily average not exceeding 95%, monthly average not exceeding 90%. 4
Water vapor pressure
daily average not exceeding 2.2 kPa, monthly average not exceeding 1.8 kPa. 5. When temperature drops sharply, condensation may occur, accompanied by pollution. This product is suitable for the following two environmental conditions more severe than normal conditions: a. Infrequent condensation (average no more than twice per month) with light pollution
Note
* Storage and transport at -30°C is permitted. For areas with altitude exceeding 2000 m, handle according to the Technical Requirements for High-voltage Apparatus for Plateau Special Environmental Conditions (GB/T 20635-2006). When altitude does not exceed 2000 m, low-voltage auxiliary equipment requires no measures. When actual operating conditions differ from the above, the user and manufacturer shall negotiate
Rated operating voltage
kV 12
Rated operating current
A 630, 125
Rated frequency
Hz 50
Rated short-circuit breaking current
kA 20, 31.5
Rated short-circuit making current (peak)
kA 50, 80
Rated short-time withstand duration
s 4
Rated short-time withstand current
kA 20, 25, 31.5
Rated peak withstand current
kA 50, 63, 80
Rated short-time power-frequency withstand voltage
kV/1min 42
Rated lightning impulse withstand voltage
kV 75

Full product details

Overview

HXGN fixed-type AC metal-enclosed switchgear. The HXGN□-12 series AC metal ring-main switchgear uses an SF6 load-break switch as the main switch, with the entire enclosure air-insulated. It is a compact, extensible metal-enclosed ring-main switchgear suitable for distribution automation. It features simple structure, flexible operation, reliable interlocking and easy installation. It provides corresponding technical solutions for various applications and user requirements. The load-break switch and circuit breaker can be operated manually or electrically; with optional electric operating mechanisms and communication devices, distribution automation functions can be achieved.

Operating environment

1. Ambient air temperature: upper limit +40°C, lower limit -10°C in general areas. 2. Altitude: not exceeding 2000 m. 3. Humidity: relative humidity daily average not exceeding 95%, monthly average not exceeding 90%. 4. Water vapor pressure: daily average not exceeding 2.2 kPa, monthly average not exceeding 1.8 kPa. 5. When temperature drops sharply, condensation may occur, accompanied by pollution. This product is suitable for the following two environmental conditions more severe than normal conditions: a. Infrequent condensation (average no more than twice per month) with light pollution; b. Generally no condensation (average no more than twice per month) with relatively severe pollution. 6. Locations without fire or explosion hazards and without severe pollution or gases sufficient to corrode metals and damage insulation. 7. Locations without severe vibration, shock, or vertical inclination not exceeding 8°. Note: * Storage and transport at -30°C is permitted. For areas with altitude exceeding 2000 m, handle according to the Technical Requirements for High-voltage Apparatus for Plateau Special Environmental Conditions (GB/T 20635-2006). When altitude does not exceed 2000 m, low-voltage auxiliary equipment requires no measures. When actual operating conditions differ from the above, the user and manufacturer shall negotiate.

Technical parameters

Rated operating voltage: kV 12; Rated operating current: A 630, 125; Rated frequency: Hz 50; Rated short-circuit breaking current: kA 20, 31.5; Rated short-circuit making current (peak): kA 50, 80; Rated short-time withstand duration: s 4; Rated short-time withstand current: kA 20, 25, 31.5; Rated peak withstand current: kA 50, 63, 80; Rated short-time power-frequency withstand voltage: kV/1min 42; Rated lightning impulse withstand voltage: kV 75

Dimensions

Height/mm 2000, 2200; Width/mm 650, 850; Depth/mm 900; Weight (kg) 300~600

Product features

The ring-main unit enclosure is assembled from machined parts, with protection rating IP3X and reliable mechanical interlocking and misoperation prevention functions. Main features: 1. The enclosure structure is assembled from 2 mm thick aluminum-zinc coated steel sheets, with pressure relief openings at the rear. 2. The busbar compartment is located at the top and connects adjacent switchgear; the load-break switch compartment is an independent unit, internally filled with SF6. 3. The cable compartment is mainly used for cable connections. 4. The mechanism compartment contains the operating mechanism and mechanism interlocks, as well as position indication, auxiliary contacts, trip coils, live-line indication, etc. 5. Pressure relief openings at the rear of the enclosure release gas pressure generated during internal arc faults. 6. Enclosure protection rating IP4X; with the handcart compartment door open, protection rating IP2X. Grounding device: A separate grounding copper bar is installed in the cable compartment; this bar can run through adjacent enclosures and makes good contact with the enclosure. This grounding bar is used for directly grounded components. Since the entire enclosure is assembled from aluminum-zinc coated steel sheets, the entire enclosure is in a well-grounded state, ensuring safety for operating personnel touching the enclosure. Mechanical interlocking: Misoperation prevention interlocking device. The switchgear has a reliable interlocking device providing reliable safety and protection for operators and equipment, with the following functions: 1. The circuit breaker can be opened or closed only when the grounding switch is in the open position. 2. When energizing, close the enclosure door, then open the grounding switch, and close the load-break switch. 3. When de-energizing, open the load-break switch, close the grounding switch, and then open the enclosure door.